Wire gauge & ampacity (NEC)
Voltage Drop Calculator | NEC Compliant Wire Sizing Tool
NEC-compliant voltage drop and wire sizing. Single and three-phase, copper or aluminum, wire size chart.
By Jeff Beem
Circuit basics
Conductor specs
Load
Results
Information hub
Why wire size and run length matter for voltage drop, and how NEC guidance fits in.
Water pressure analogy
Voltage behaves like water pressure; current like flow rate. Push water through a long, thin hose and pressure drops along the way, friction eats it. Same with wire: resistance and distance cut voltage before it reaches the load. Thinner wire and longer runs mean more drop. Upsize the conductor and you get less resistance, like switching to a wider hose.
Formula variables
This calculator uses the standard NEC-style AC voltage drop formula. Each symbol:
- One-way length (ft). Double for round trip.
- Load current (A). Higher current = more drop.
- Resistance (Ω/1000 ft, NEC Table 8).
- Reactance (Ω/1000 ft, NEC Table 9).
- Power factor. Use 1.0 for resistive loads.
NEC guidance: 3% and 5% limits
The National Electrical Code does not enforce a maximum voltage drop, but it does provide guidance in the Informational Notes. Two limits matter:
- Branch circuit (3%): For the run from the last overcurrent device to the outlet or load. Keeping branch drop under 3% helps avoid flickering lights and sluggish motors at the point of use.
- Total system (5%): For feeder plus branch combined. This applies when you have a long feeder feeding a panel, then branch circuits from that panel. The total drop from source to load should stay under 5%.
Exceeding these values won’t fail an inspection, but it can lead to equipment problems and wasted energy. This calculator highlights results in amber when drop exceeds 3%.
Wire size chart: AWG to resistance
Reference copper resistance (Ω/1000 ft) at 75°C, illustrative; verify against current NEC tables for your installation.
| AWG | Diameter (mm) | Area (mm²) | Copper R (Ω/1000 ft) |
|---|---|---|---|
| 18 | 1.02 | 0.82 | 7.95 |
| 16 | 1.29 | 1.31 | 4.99 |
| 14 | 1.63 | 2.08 | 3.26 |
| 12 | 2.05 | 3.31 | 1.98 |
| 10 | 2.59 | 5.26 | 1.24 |
| 8 | 3.26 | 8.37 | 0.78 |
| 6 | 4.11 | 13.3 | 0.49 |
| 4 | 5.19 | 21.2 | 0.31 |
| 2 | 6.54 | 33.6 | 0.19 |
| 1 | 7.35 | 42.4 | 0.15 |
| 1/0 | 8.25 | 53.5 | 0.12 |
| 2/0 | 9.27 | 67.4 | 0.10 |
| 3/0 | 10.4 | 85.0 | 0.08 |
| 4/0 | 11.7 | 107 | 0.06 |
Voltage Drop Formulas & Quick Reference
NEC Chapter 9 Tables 8 and 9 drive the math. Single-phase uses the 2× factor for out-and-back; three-phase uses √3. Resistive loads use power factor 1.0; motors typically 0.85–0.9.
Formulas & Variables
Three Phase
12V DC (no reactance)
Variables
Power Factor
When to Upsize
Voltage Drop Calculator: NEC Wire Sizing & Distance
Calculate voltage drop for single-phase and three-phase circuits using NEC Table 8 and Table 9. Wire size chart, copper vs aluminum, conduit type. Free wire sizing tool for electricians and DIY.
What This Calculator Does
- Inputs:System voltage, phase (single/three/DC), power factor, wire material, conduit type, AWG gauge, one-way distance, and load current.
- Outputs:Voltage drop in volts, drop as a percentage, and a pass/warning indicator based on NEC recommendations.
How the Math Works
- Single-Phase:
- Three-Phase:
- DC (no reactance):
- Variables:= one-way length (ft), = current (A), = resistance (Ω/1000 ft, NEC Table 8), = reactance (Ω/1000 ft, NEC Table 9), = power factor.
- Worked Example:240V single-phase, 20A, 150 ft one-way, 10 AWG copper in PVC (R = 1.21, X = 0.044), PF = 1.0: V_drop = 2 × 150 × 20 × 1.21 / 1000 ≈ 7.26 V (3.0%). Right at the NEC threshold, upsizing to 8 AWG drops it to about 1.9%.
How to Use This Calculator
- System Voltage & Phase:Select the voltage (120, 208, 240, 277, or 480 V) and phase configuration (single-phase, three-phase, or DC). For 12V DC and solar, choose DC mode.
- Wire Material & Conduit:Choose copper or aluminum, then select conduit type (PVC, aluminum, or steel). Steel conduit increases inductive reactance on AC circuits.
- Wire Gauge & Power Factor:Pick an AWG size from the chart (14 AWG through 4500 kcmil). Set the power factor, 1.0 for resistive loads, 0.85–0.9 for motors.
- Distance & Current:Enter the one-way wire run length in feet or meters and the load current in amps.
- Read the Results:The output shows voltage drop in volts and as a percentage. Results above 3% are flagged amber per NEC informational notes. Try a larger wire size if the drop is too high.
Wire Size Chart & Voltage Drop
3% Branch, 5% Total: NEC Voltage Drop Limits
Copper vs Aluminum Wire Sizing
12V DC, Solar, and Low-Voltage Runs
Voltage Drop Calculator FAQ
What is the maximum allowed voltage drop?
How do I calculate voltage drop for 12V DC?
How does wire material (Copper vs Aluminum) affect drop?
Does conduit type actually matter?
How do I reduce voltage drop in a long run?
What happens if my voltage drop is too high?
Electronics Reference Note
Educational Use: These tools use standard electrical formulas (e.g., Ohm's Law, NEC voltage drop) for learning, hobby projects, and general reference, not for licensed electrical work or safety-critical installations.
Verification Recommended: Wire sizing, voltage drop, and circuit design depend on local codes, ambient conditions, and load profiles. For real installations, consult a qualified electrician or engineer.
Not Professional Advice: This site does not provide electrical or engineering advice. All calculations run locally in your browser; no data is stored or transmitted.