Skip to main content

Wire gauge & ampacity (NEC)

Voltage Drop Calculator | NEC Compliant Wire Sizing Tool

NEC-compliant voltage drop and wire sizing. Single and three-phase, copper or aluminum, wire size chart.

By Jeff Beem

01

Circuit basics

02

Conductor specs

03

Load

04

Results

Voltage drop
5.940 V
4.95%
Exceeds NEC 3% branch recommendation
Voltage at end
114.06 V
Efficiency
95.05%
0%3% branch5% total6%
Drop at 4.95%
Work shown

Information hub

Why wire size and run length matter for voltage drop, and how NEC guidance fits in.

Water pressure analogy

Voltage behaves like water pressure; current like flow rate. Push water through a long, thin hose and pressure drops along the way, friction eats it. Same with wire: resistance and distance cut voltage before it reaches the load. Thinner wire and longer runs mean more drop. Upsize the conductor and you get less resistance, like switching to a wider hose.

Formula variables

This calculator uses the standard NEC-style AC voltage drop formula. Each symbol:

LL
One-way length (ft). Double for round trip.
II
Load current (A). Higher current = more drop.
RR
Resistance (Ω/1000 ft, NEC Table 8).
XX
Reactance (Ω/1000 ft, NEC Table 9).
cosθ\cos\theta
Power factor. Use 1.0 for resistive loads.

NEC guidance: 3% and 5% limits

The National Electrical Code does not enforce a maximum voltage drop, but it does provide guidance in the Informational Notes. Two limits matter:

  • Branch circuit (3%): For the run from the last overcurrent device to the outlet or load. Keeping branch drop under 3% helps avoid flickering lights and sluggish motors at the point of use.
  • Total system (5%): For feeder plus branch combined. This applies when you have a long feeder feeding a panel, then branch circuits from that panel. The total drop from source to load should stay under 5%.

Exceeding these values won’t fail an inspection, but it can lead to equipment problems and wasted energy. This calculator highlights results in amber when drop exceeds 3%.

Wire size chart: AWG to resistance

Reference copper resistance (Ω/1000 ft) at 75°C, illustrative; verify against current NEC tables for your installation.

18
Diameter1.02 mmArea0.82 mm²Copper R7.95 Ω/1000 ft
16
Diameter1.29 mmArea1.31 mm²Copper R4.99 Ω/1000 ft
14
Diameter1.63 mmArea2.08 mm²Copper R3.26 Ω/1000 ft
12
Diameter2.05 mmArea3.31 mm²Copper R1.98 Ω/1000 ft
10
Diameter2.59 mmArea5.26 mm²Copper R1.24 Ω/1000 ft
8
Diameter3.26 mmArea8.37 mm²Copper R0.78 Ω/1000 ft
6
Diameter4.11 mmArea13.3 mm²Copper R0.49 Ω/1000 ft
4
Diameter5.19 mmArea21.2 mm²Copper R0.31 Ω/1000 ft
2
Diameter6.54 mmArea33.6 mm²Copper R0.19 Ω/1000 ft
1
Diameter7.35 mmArea42.4 mm²Copper R0.15 Ω/1000 ft
1/0
Diameter8.25 mmArea53.5 mm²Copper R0.12 Ω/1000 ft
2/0
Diameter9.27 mmArea67.4 mm²Copper R0.10 Ω/1000 ft
3/0
Diameter10.4 mmArea85.0 mm²Copper R0.08 Ω/1000 ft
4/0
Diameter11.7 mmArea107 mm²Copper R0.06 Ω/1000 ft

Voltage Drop Formulas & Quick Reference

NEC Chapter 9 Tables 8 and 9 drive the math. Single-phase uses the 2× factor for out-and-back; three-phase uses √3. Resistive loads use power factor 1.0; motors typically 0.85–0.9.

Formulas & Variables

Single Phase

Vdrop=2LI(Rcosθ+Xsinθ)1000V_{\text{drop}} = \frac{2 L I (R \cos\theta + X \sin\theta)}{1000}

Three Phase

Vdrop=3LI(Rcosθ+Xsinθ)1000V_{\text{drop}} = \frac{\sqrt{3} L I (R \cos\theta + X \sin\theta)}{1000}

12V DC (no reactance)

Vdrop=2LIR1000V_{\text{drop}} = \frac{2 L I R}{1000}

Variables

LL = one-way length (ft)
II = current (A)
RR = resistance (Ω/1000 ft, Table 8)
XX = reactance (Ω/1000 ft, Table 9)
cosθ\cos\theta = power factor

Power Factor

cosθ=1\cos\theta = 1 for resistive loads (heaters, incandescent). Motors often 0.85–0.9. Lower PF increases the reactance term.

When to Upsize

If drop exceeds 3% on a branch or 5% total, go up a wire size or shorten the run. See the wire size chart in the hub above for AWG resistance values.

Voltage Drop Calculator: NEC Wire Sizing & Distance

Calculate voltage drop for single-phase and three-phase circuits using NEC Table 8 and Table 9. Wire size chart, copper vs aluminum, conduit type. Free wire sizing tool for electricians and DIY.

What This Calculator Does

This voltage drop calculator determines how much voltage is lost along a wire run for single-phase, three-phase, or DC circuits. Enter your system voltage, wire material (copper or aluminum), conduit type, wire gauge, one-way distance, and load current. The tool pulls resistance values from NEC Table 8 and reactance values from NEC Table 9 to compute the drop in both volts and percentage. Results are flagged amber when they exceed the NEC-recommended 3% branch-circuit threshold. Use it for residential wiring, commercial installations, solar arrays, or 12V DC runs.
  • Inputs:
    System voltage, phase (single/three/DC), power factor, wire material, conduit type, AWG gauge, one-way distance, and load current.
  • Outputs:
    Voltage drop in volts, drop as a percentage, and a pass/warning indicator based on NEC recommendations.

How the Math Works

Voltage drop depends on wire resistance, reactance, distance, current, and phase configuration. The calculator uses NEC Chapter 9 tables for accurate R and X values per wire size and conduit type:
  • Single-Phase:
    Vdrop=2LI(Rcosθ+Xsinθ)1000V_{\text{drop}} = \frac{2 L I (R \cos\theta + X \sin\theta)}{1000}
  • Three-Phase:
    Vdrop=3LI(Rcosθ+Xsinθ)1000V_{\text{drop}} = \frac{\sqrt{3}\, L I (R \cos\theta + X \sin\theta)}{1000}
  • DC (no reactance):
    Vdrop=2LIR1000V_{\text{drop}} = \frac{2 L I R}{1000}
  • Variables:
    LL = one-way length (ft), II = current (A), RR = resistance (Ω/1000 ft, NEC Table 8), XX = reactance (Ω/1000 ft, NEC Table 9), cosθ\cos\theta = power factor.
  • Worked Example:
    240V single-phase, 20A, 150 ft one-way, 10 AWG copper in PVC (R = 1.21, X = 0.044), PF = 1.0: V_drop = 2 × 150 × 20 × 1.21 / 1000 ≈ 7.26 V (3.0%). Right at the NEC threshold, upsizing to 8 AWG drops it to about 1.9%.

How to Use This Calculator

Size your wire correctly by following these steps:
  • System Voltage & Phase:
    Select the voltage (120, 208, 240, 277, or 480 V) and phase configuration (single-phase, three-phase, or DC). For 12V DC and solar, choose DC mode.
  • Wire Material & Conduit:
    Choose copper or aluminum, then select conduit type (PVC, aluminum, or steel). Steel conduit increases inductive reactance on AC circuits.
  • Wire Gauge & Power Factor:
    Pick an AWG size from the chart (14 AWG through 4500 kcmil). Set the power factor, 1.0 for resistive loads, 0.85–0.9 for motors.
  • Distance & Current:
    Enter the one-way wire run length in feet or meters and the load current in amps.
  • Read the Results:
    The output shows voltage drop in volts and as a percentage. Results above 3% are flagged amber per NEC informational notes. Try a larger wire size if the drop is too high.

Wire Size Chart & Voltage Drop

A voltage drop calculator answers: will my wire handle this run? Enter voltage (120, 208, 240, 480 V), phase (1 or 3), material (copper or aluminum), conduit (PVC, aluminum, steel), wire size from the AWG wire size chart (14 through 4500 kcmil), one-way distance in feet or meters, and load current. The tool uses NEC Table 8 for resistance and Table 9 for reactance, so the results match what you'd get with the standard formulas.

3% Branch, 5% Total: NEC Voltage Drop Limits

NEC Informational Notes recommend keeping branch-circuit drop under 3% and total system drop (feeder + branch) under 5%. These aren't enforceable limits, inspectors won't fail you, but exceeding them often leads to dim lights, hot motors, and efficiency loss. Contractors and engineers routinely design to these targets. The calculator flags results in amber when drop tops 3%.

Copper vs Aluminum Wire Sizing

Copper has lower resistance per gauge than aluminum, so you can use smaller wire for the same drop. Aluminum costs less but needs one size up to match; it also demands proper torque on lugs and antioxidant. Conduit choice matters too: steel adds inductive reactance versus PVC or aluminum. Use the calculator to compare wire sizes before ordering.

12V DC, Solar, and Low-Voltage Runs

For 12V DC, RV, solar, or automotive wiring, reactance is zero, use the DC formula. The calculator's power factor of 1.0 covers it. Long low-voltage runs are where drop hurts most: a 0.5 V drop on 120 V is minor; on 12 V it's over 4%. Upsize early for DC and low-voltage runs.

Voltage Drop Calculator FAQ

What is the maximum allowed voltage drop?

The NEC doesn't set a hard limit, but Informational Notes suggest 3% for branch circuits and 5% for feeder plus branch combined. Most electricians aim for these thresholds, going over can cause flicker, motors running hot, and wasted power.

How do I calculate voltage drop for 12V DC?

For DC, reactance is zero. Use Vdrop=2LIR/1000V_{\text{drop}} = 2 L I R / 1000, the 2 accounts for out-and-back. Pull R from NEC Table 8 for your wire size and material. Example: 12 V, 10 A, 20 ft one-way, 12 AWG copper (R ≈ 1.98 Ω/1000 ft): Vdrop0.79V_{\text{drop}} \approx 0.79 V.

How does wire material (Copper vs Aluminum) affect drop?

Aluminum has about 61% of copper's conductivity, so for the same gauge it has roughly 1.6× the resistance. To get similar drop, you typically go one size larger with aluminum (e.g. 10 AWG Al where 12 AWG Cu would work). Aluminum saves money but needs proper lugs and torque.

Does conduit type actually matter?

It does. Steel conduit is magnetic and boosts inductive reactance; PVC and aluminum conduit are non-magnetic. NEC Table 9 gives different X values for each. On long runs or motor circuits, the difference can be noticeable.

How do I reduce voltage drop in a long run?

Upsize the wire, shorten the run, or switch to copper from aluminum. For AC, non-magnetic conduit (PVC or aluminum) lowers reactance. Try different wire sizes in the calculator to see the impact.

What happens if my voltage drop is too high?

Motors pull more current at low voltage and run hotter, life drops. Lights dim or flicker. Gear can brown out. You lose efficiency because power goes to heating the wire. Fix it by larger wire, shorter distance, or splitting the load.

Electronics Reference Note

Educational Use: These tools use standard electrical formulas (e.g., Ohm's Law, NEC voltage drop) for learning, hobby projects, and general reference, not for licensed electrical work or safety-critical installations.

Verification Recommended: Wire sizing, voltage drop, and circuit design depend on local codes, ambient conditions, and load profiles. For real installations, consult a qualified electrician or engineer.

Not Professional Advice: This site does not provide electrical or engineering advice. All calculations run locally in your browser; no data is stored or transmitted.

© 2026 CalcRegistry Reference Last Logic Update: May 2026Free Online Utility Tools